Series HI
| INVERTER: minimum input voltage | 400 V | |
| Suction valve | 42 s. | [mm] |
| Max operating current | 45.0 | [A] |
| Frequency max. | 75.0 | [Hz] |
| Displacement @ 50 Hz | 48,82 | [m³/h] |
| Frequency min. | 20.0 | [Hz] |
| Net weight | 140 | [kg] |
| Type of electrical connection | 400 V / 3 / 50 Hz DOL | |
| Discharge valve | 35 s. | [mm] |
| Stroke | 45 | [mm] |
| Locked rotor current | 177.0 | [A] |
| Bore | 63 | [mm] |
| No. cylinders | 4 | |
| Oil charge | 2,5 | [L] |
A - Oil sight glass
B - Oil charge plug
C - Low pressure connection
D - High pressure connection
E - Oil drain plug
F - Crankcase heater
DL - Discharge service valve
SL - Suction service valve